Rebooting other stuff

There are also a number of CPU's running EPICS and other controls software. If controls for High Voltage or Magnets are not functioning, they may need to be rebooted. Table 2.27 gives the location and function of several CPU reboot buttons not already listed in Table 2.26. Many of these resets are accessed by running the application rebootpanel from an X-session logged in to cdaqs1 (user cdaq).

Table 2.27: EPICS IOC and Device reboot button locations
Function CPU CPU Location Reboot
      Button
HMS Cryo & Rotation vmec2 HMS Hut vmec2
SOS HV vmec6 CH03B13,1-11 vmec6
Møller Cryo,Tgt,Sol vmec10 Near Power Supplies vmec10 \dag
Møller Quads vmec11 Near Power Supplies vmec11 ***
Beam Curr, EPICS Rptr vmec15 CH03B12-left vmec15
HMS Hall Probes Read vmec18 HMS Shield House vmec18
SOS mag controls vmec19 Near Power Supplies vmec19
HMS HV vmec20 CH03B13,1-1 vmec20
Slit Box Controls   Pivot Racks slitbox
Solid Tgt. Rotator   Behind Green Wall STGTROT
Solid Tgt. Lifter   Behind Green Wall STGTLif
Møller Coll & Tgt   Behind Green Wall MolCol
HMS Dipole PS Comm. Eldatic HMS Shield House PDS
HMS Dipole PS Contr. Dipole HMS Shield House Eldatic
HMS Q1 Controls HMS Q1 HMS Shield House HMSQ1
HMS Q2 Controls HMS Q2 HMS Shield House HMSQ2
HMS Q3 Controls HMS Q3 HMS Shield House HMSQ3
Fast Raster IOC IOCHLC2 HC01Z07 IOCHLC2 * **
Items in italics refer to buttons on the rebootpanel GUI.
\dagIf you reboot VMEC10 (iochc10) you must then RESTORE the Moller cryo saved parameters. Use the popup menu given by the small blue box on the bottom center of the Møller cryo overview page. Do a "iochc10:NORMAL RESTORE" and keep hitting ENTER when the popup dialog screen prompts you.
* May also be reset from MCC using a software reset.
** This reset generates an FSD! Contact MCC first.
*** Do not reboot vmec11 (iochc11) unless requested by MCC.


A reset switch has been moved up to the counting house for the HMS carriage rotation. One should use this button if the rotation GUI shows interlocks. If the interlock is real, then the reset button will not clear the interlock. One needs to press and hold the button for at least 1 to 2 seconds to clear the Sumito motor controllers. The reset button is located next to the rotation kill button, on the left section of the counting room console.