• Main INDEX
  • Monthly INDEX
  • PREV
  • NEXT

    User name mckee

    Log entry time 12:49:54 on September 8,2001

    Entry number 40072

    keyword=Cryo problem

    At about 12:00 I noticed the buffer dewar was overfull, with a level of about 95%. The cold return temp was 4.4K, and the PID settings for EV9180 showed a minimum valve position of 50 and a maximum of 48!
    I verified that the EV9180 and EV9180A PID settings had not been tampered with, and then did some tests. First, by putting EV9180A in manual mode, I could not get the minimum valve position of EV9180 to change. This explains why the valve was open so much. I tried toggling between manual and auto mode with no success.
    Currently, EV9180 is in manual mode, set to a position of 35%. I reached this by slowly changing the valve position in increments of 2% each.
    EV9180 should be left in manual mode until the buffer dewar level lowers to 65%. It may take more than one magnet fill to consume this quantity of helium.