Difference between revisions of "E-Detector Motion System"
From PolWiki
Jump to navigationJump to searchLine 3: | Line 3: | ||
* cd MEDM/compton | * cd MEDM/compton | ||
* edm -x HLC_E_CompED.edl | * edm -x HLC_E_CompED.edl | ||
+ | |||
+ | === Parking the detector === | ||
+ | During standard running conditions, the above GUI at top left shows '''X = -8.6890'''. We park it to Garage whenever | ||
+ | # when we expect beam to be re-tuned through the chicane after a beam studies or a long down | ||
+ | # we are sure of not running for a couple of days at a stretch | ||
+ | # when the beam is intended to be taken straight through (instead of the chicane) | ||
+ | |||
+ | The procedure for parking is: | ||
+ | # The detector can be moved only when the beam is off. | ||
+ | # Call MCC and request to mask Compton electron detector motion FSD. Make sure that they have masked before starting to move. | ||
+ | # In the drop-down box on the left-middle of the e-detector motion GUI, choose 'GO HOME' You should start seeing the box indicating that the detector is moving gets highlighted by yellow. | ||
+ | # Check to see that the motion is complete. You see the position readback to be '''X=0.0000''' and the yellow highlighting is off. | ||
+ | # From the same drop-down menu, now select the 'Garage' and the detector start going to Garage. | ||
+ | # On completion of this motion again, the yellow highlighting goes away and the detector is well parked now. | ||
== General Description == | == General Description == |
Revision as of 11:42, 7 April 2011
Motion Mechanism GUI
- login to cdaql* as cvxwrks
- cd MEDM/compton
- edm -x HLC_E_CompED.edl
Parking the detector
During standard running conditions, the above GUI at top left shows X = -8.6890. We park it to Garage whenever
- when we expect beam to be re-tuned through the chicane after a beam studies or a long down
- we are sure of not running for a couple of days at a stretch
- when the beam is intended to be taken straight through (instead of the chicane)
The procedure for parking is:
- The detector can be moved only when the beam is off.
- Call MCC and request to mask Compton electron detector motion FSD. Make sure that they have masked before starting to move.
- In the drop-down box on the left-middle of the e-detector motion GUI, choose 'GO HOME' You should start seeing the box indicating that the detector is moving gets highlighted by yellow.
- Check to see that the motion is complete. You see the position readback to be X=0.0000 and the yellow highlighting is off.
- From the same drop-down menu, now select the 'Garage' and the detector start going to Garage.
- On completion of this motion again, the yellow highlighting goes away and the detector is well parked now.
General Description
- The electron detector is connected to the QWAD using the custom made [Flex-cable]. The detector is placed inside the vacuum-can whereas the QWAD boards are connected from outside the vacuum-can using appropriate flanges used between the Flex-cable and the QWAD. The connection between e-detector and the QWAD (if the vacuum - can was transparent) can be depicted as in the attached picture.
- The electron detector vacuum - can has a motion mechanism to allow us to move the detector vertically in and out of the beam along with the ability to rotate the detector facing the beam. A schematic view of the assembly can be seen here.
- We are using a stepping motor identified as KML062S04 for vertical motion ( data sheet ) of detector using a MDC accuator ( specifications ). This motor is being controlled by a single axis IDC Controller (User Manual). The Motion Controller can be controlled through its keypad or via computer terminal after installing its software provided on their website
- Motion Controller:
- Vertically downward motion of the actuator is referred to as 'positive' direction based on the current settings of the controller.
- All numbers displayed on the controller uses appropriate units of inch and second
- The Actuator has 3 physically verifiable positions which correspond to a switch on the actuator.
- EOT+ (end of travel switch in positive direction) will not be used
- EOT- (end of travel switch in negative direction) used as Garage
- Home
- Current Controller Settings:
- Current: 1.5A
- Resolution: 18000
- Inductance: 16 mH
- Direction: positive
- Distance Unit: cm
- Velocity: cm/s
- Acceleration Unit: cm/s^2
- Gear Ratio: (GR) = 10:1
Operation
At EOT- (physically top most) the actuator position read back (as seen on the controller display) is
-3.7833 00000000 00000000
AC.02 VE.1 DA2 GO
+2.0000 00000000 00000000
AC.02 VE.1 DA1 GO
+1.0000 00000000 00000000
AC.02 VE.1 DA-2 GO
-2.0000 00000000 00000000
AC.02 VE.1 DI1 GO
-1.0000 00000000 00000000
Controller Settings
We shall maintain two files for the controller settings
- The most recent settings updated on Nov 29, 2010
- The last working settings updated on Oct 14, 2010
The list of programs loaded in the current configuration are
- Prog 1: Go Home;
- Prog 2: 2 cm above chicane beam;
- Prog 3: Garage, EOT-;
- Prog 4: 5 mm above chicane beam
- Prog 10: Incremental motion : -2 mm
- Prog 11: Incremental motion : -1 mm
- Prog 12: Incremental motion : +1 mm
- Prog 13: Incremental motion : +2 mm
- Prog 14: Incremental motion : -0.5 mm
- Prog 15: Incremental motion : +0.5 mm
- Prog 16: Incremental motion : -0.2 mm
- Prog 17: Incremental motion : +0.2 mm
- Prog 98: Motor Stopper