Difference between revisions of "E-Detector Motion System"
From PolWiki
Jump to navigationJump to searchLine 54: | Line 54: | ||
We shall maintain two files for the controller settings | We shall maintain two files for the controller settings | ||
− | * The [[Media:EDet_motion_controller_current.txt |most recent settings]] updated on | + | * The [[Media:EDet_motion_controller_current.txt |most recent settings]] updated on Nov 29, 2010 |
− | + | * The [[Media:Edet_motion_controller_settings.txt |last working settings]] updated on Oct 14, 2010 | |
− | * The [[Media:Edet_motion_controller_settings.txt |last working settings]] updated on Oct | ||
Revision as of 06:10, 30 November 2010
Motion Mechanism GUI
- login to cdaql* as cvxwrks
- cd MEDM/compton
- edm -x HLC_E_CompED.edl
General Description
- The electron detector is connected to the QWAD using the custom made [Flex-cable]. The detector is placed inside the vacuum-can whereas the QWAD boards are connected from outside the vacuum-can using appropriate flanges used between the Flex-cable and the QWAD. The connection between e-detector and the QWAD (if the vacuum - can was transparent) can be depicted as in the attached picture.
- The electron detector vacuum - can has a motion mechanism to allow us to move the detector vertically in and out of the beam along with the ability to rotate the detector facing the beam. A schematic view of the assembly can be seen here.
- We are using a stepping motor identified as KML062S04 for vertical motion ( data sheet ) of detector using a MDC accuator ( specifications ). This motor is being controlled by a single axis IDC Controller (User Manual). The Motion Controller can be controlled through its keypad or via computer terminal after installing its software provided on their website
- Motion Controller:
- Vertically downward motion of the actuator is referred to as 'positive' direction based on the current settings of the controller.
- All numbers displayed on the controller uses appropriate units of inch and second
- The Actuator has 3 physically verifiable positions which correspond to a switch on the actuator.
- EOT+ (end of travel switch in positive direction) will not be used
- EOT- (end of travel switch in negative direction) used as Garage
- Home
- Current Controller Settings:
- Current: 1.5A
- Resolution: 18000
- Inductance: 16 mH
- Direction: positive
- Distance Unit: cm
- Velocity: cm/s
- Acceleration Unit: cm/s^2
- Gear Ratio: (GR) = 10:1
Operation
At EOT- (physically top most) the actuator position read back (as seen on the controller display) is
-3.7833 00000000 00000000
AC.02 VE.1 DA2 GO
+2.0000 00000000 00000000
AC.02 VE.1 DA1 GO
+1.0000 00000000 00000000
AC.02 VE.1 DA-2 GO
-2.0000 00000000 00000000
AC.02 VE.1 DI1 GO
-1.0000 00000000 00000000
Controller Settings
We shall maintain two files for the controller settings
- The most recent settings updated on Nov 29, 2010
- The last working settings updated on Oct 14, 2010
The list of programs loaded in the current configuration are
- Prog 1: Go Home;
- Prog 2: 2 cm above chicane beam;
- Prog 3: Garage, EOT-;
- Prog 4: 5 mm above chicane beam
- Prog 10: Incremental motion : -2 mm
- Prog 11: Incremental motion : -1 mm
- Prog 12: Incremental motion : +1 mm
- Prog 13: Incremental motion : +2 mm
- Prog 14: Incremental motion : -0.5 mm
- Prog 15: Incremental motion : +0.5 mm
- Prog 16: Incremental motion : -0.2 mm
- Prog 17: Incremental motion : +0.2 mm
- Prog 98: Motor Stopper