Difference between revisions of "Beam Time Accounting EPICS Calculations"
From HallCWiki
Jump to navigationJump to search (Created page with "The Beam Time Accounting form has an option "Load from EPICS" that is supposed to populate the BTA form with trial values of beam and hall availability. (Which the shift leade...") |
|||
(One intermediate revision by one other user not shown) | |||
Line 1: | Line 1: | ||
− | The Beam Time Accounting form has an option "Load from EPICS" that is supposed to populate the BTA form with trial values of beam and hall availability. (Which the shift leader can then update/correct based on other factors.) The trial values depend on formulas in EPICS CALC records. The hall determines these formulas | + | The Beam Time Accounting form has an option "Load from EPICS" that is supposed to populate the BTA form with trial values of beam and hall availability. (Which the shift leader can then update/correct based on other factors.) The trial values depend on formulas in EPICS CALC records. The hall determines these formulas. |
+ | First try running <code>go_bta_config</code> under the ''cdaq'' account and make sure the settings are correct. | ||
+ | |||
+ | If the above helper GUI doesn't solve the issue, then the underlying formulas may have been deleted. | ||
To restore the formulas, run "jmenu", search on "bta" and select "Hall C BTA". Then fill in the fields to match this figure. | To restore the formulas, run "jmenu", search on "bta" and select "Hall C BTA". Then fill in the fields to match this figure. | ||
− | [[ | + | [[File:BTAConfig.png|800px]] |
Alternatively, the following commands can be run from hccuser@hlal01. These commands are in the script btafix.sh in the hccuser account on hlal01. | Alternatively, the following commands can be run from hccuser@hlal01. These commands are in the script btafix.sh in the hccuser account on hlal01. |
Latest revision as of 15:17, 10 September 2021
The Beam Time Accounting form has an option "Load from EPICS" that is supposed to populate the BTA form with trial values of beam and hall availability. (Which the shift leader can then update/correct based on other factors.) The trial values depend on formulas in EPICS CALC records. The hall determines these formulas.
First try running go_bta_config
under the cdaq account and make sure the settings are correct.
If the above helper GUI doesn't solve the issue, then the underlying formulas may have been deleted. To restore the formulas, run "jmenu", search on "bta" and select "Hall C BTA". Then fill in the fields to match this figure.
Alternatively, the following commands can be run from hccuser@hlal01. These commands are in the script btafix.sh in the hccuser account on hlal01.
caput HLC:bta_bm_present.CALC "A>B" caput HLC:bta_bm_present.INPA "ibcm1 CA NMS" caput HLC:bta_bm_present.INPB "HC:beamok_limit CA NMS" caput HLC:bta_daq_used.CALC "A=1" caput HLC:bta_daq_used.INPA "HC:exp_ready CA NMS" caput HLC:bta_experiment_ready.CALC "A=1" caput HLC:bta_experiment_ready.INPA "HC:exp_ready CA NMS" caput HLC:bta_config_change.CALC "A=2" caput HLC:bta_config_change.INPA "HC:exp_ready CA NMS"