Charge Feedback Parity DAQ

From HallCWiki
Jump to navigationJump to search

The Charge Asymmetry Feedback system is controlled by the Hall A Parity DAQ.

When Hall A is in production mode, the Hall A shift crew will manage the Parity DAQ and control feedback for both Hall A and Hall C beams.

If the Hall A Counting House is not staffed, then Hall C must negotiate with the Parity group to ensure that the Parity DAQ is still running.

  • This must be running for all 3He production data! (And should be running in general.)
    • The state of this system is monitored in the Hall C alarm handler, and can be overseen by the Hall C Shift crew using the stripchart on the left large wall display (see below).

Qasym Stripcharts

Instructions

System running under VNC session from Aug 2020

System run via ssh tunneling in Feb 2020

Useful Commands

  • go_parity Injector parity settings (IHWP status, Hall Laser IA settings, etc)
  • go_parity_feedback Bring up the Parity DAQ charge feedback VNC session (if Hall C is running alone; see below)
  • go_Qasym_stripchart Bring up the Hall C Charge Asym monitoring stripcharts (these should always be up on the big wall screens)

How to run the flipper script

  • This script need to be run when the IHWP state changes
  • stop the run (parity daq)
  • in the vnc session from above
  • ssh apar@adaq2
  • cd ~/feedback2019
  • ./FlipPCvaluesHallC You should see the hallc_IACell_setting variable change on the wall
  • ./checkPCvaules
  • start a run (parity daq)

Contacts

  • Bill Henry (Hall C)
  • Cameron Clarke (Hall A)
  • Caryn Palatchi (Hall A)