User name beaufait
Log entry time 10:59:54 on June 23, 2005
Entry number 98390
keyword=Q2 tripps
User reported dcoc trips for Q2.
I found that the DC trip level was set very close to the opperating point.
The users were running at 400 amps. Thge trip was at 450. I have moved
the trip point to 550 and am leaving the supply running at 500 amps for test.